70
protective
The failure is detected when the room temperature sensor broken or shorted over 5 sec.
The failure is detected when the temperature sensor of heater exchange broken or shorted over 5 sec.
The failure is detected when each setting data is not match after the EEPPOM self-check two times.
The failure is occur when the grounding signal is not detected after the appliance power ON.
7-2. Test the jumper terminals
Note:
When the whole machine is powered up, if the external unit does not work, to rule out the
communications failures, adopt screening method such as short circuit on the jumper terminals to see if
the external unit can be started normally or similar method.
There are two blue terminals on the outdoor control panel, as shown above.
Application: Short out the terminals, and power up the outdoor unit, then the outdoor unit may run
independently. It can be determined that there is no internal and external communication faults.
7-3. Trouble Diagnosis of Protection
Protection diagnosis of the complete machine (all types of protection during operation, i.e.
under-voltage, over-voltage and overcurrent protection)
Note:
List all types of protection that may occur to the complete machine and describe the conditions
and signs of the start, course and end of such protection.
Voltage protection
Protection against AC input over-voltage/under-voltage
Содержание ABSCI4H4S09
Страница 1: ...1 Service Manual...
Страница 20: ...20 Outdoor Units Unit All Models View Remote controller Model All Models View...
Страница 27: ...27 Indoor 1852066 1854605...
Страница 28: ...28 1854698...
Страница 29: ...29 Outdoor 1854707...
Страница 47: ...47 ASRCI4H4S18 ASRCI4H4S24 ABSCI4H4S12 ABSCI4H4S18...
Страница 50: ...50 6 2 Fan Motor Drawings attached...
Страница 74: ...74 Air Con International Inc 1802 SW 2nd St Pompano Beach FL 33069 Tel 954 771 1415 Fax 954 771 1418...