1.Conditions for protection against AC input over-voltage/under-voltage:
If the input AC voltage is greater than “protective over-voltage value” or less than “protective
under-voltage value” for five seconds, over-voltage/under-voltage protection tarts.
2.Protection actions against AC input over-voltage/under-voltage
The system stops operation.
3. Conditions for ending AC input over-voltage/under-voltage:
If the input AC voltage is lower than “the protective over-voltage value” -10V, or higher than “the
protective under-voltage value” +10V, the over-voltage/under-voltage protection will be released.
Current protection:
1.Protection against over-current
Conditions for over-current protection: if the current is equal to or greater than “current value for starting
the refrigeration current protection (E2 value)” for six seconds, over-current protection starts.
Protection actions against over-current: indoor display screen and outdoor indicator give indications, the
compressor and outdoor fan stop, but indoor fan runs normally.
Condition for ending over-current protection: when the current drops below “current value for releasing
the refrigeration current protection (E2 value)”, over-current protection will be released.
2.Frequency decreasing for over-current
Conditions for over-current
frequency decreasing
: if the current is equal to or greater than “current value
for starting the refrigeration current protective frequency decreasing (E2 value)”, over-current
frequency
decreasing
starts.
Over-current
frequency decreasing
actions: the compressor will decrease frequency at rate of (E2
value)Hz/S. The indoor and outdoor fans run.
Conditions for ending over-current
frequency decreasing
: when the current drops below “current value
for starting the refrigeration current protective prohibition of frequency rising (E2 value)”, over-current
under-clocking will be released.
3.Prohibition of frequency increasing of compressor exhausting
Conditions for prohibition of frequency rising of compressor discharge
Condition 1: in the case of frequency decreasing of compressor discharge, the discharge temperature of
Содержание ABSCI4H4S09
Страница 1: ...1 Service Manual...
Страница 20: ...20 Outdoor Units Unit All Models View Remote controller Model All Models View...
Страница 27: ...27 Indoor 1852066 1854605...
Страница 28: ...28 1854698...
Страница 29: ...29 Outdoor 1854707...
Страница 47: ...47 ASRCI4H4S18 ASRCI4H4S24 ABSCI4H4S12 ABSCI4H4S18...
Страница 50: ...50 6 2 Fan Motor Drawings attached...
Страница 74: ...74 Air Con International Inc 1802 SW 2nd St Pompano Beach FL 33069 Tel 954 771 1415 Fax 954 771 1418...