6-3. Temperature Sensor
Parameter table attached:
1. THE PARAMETER OF THE INDOOR COIL AND INDOOR ROOM SENSOR ,THE PARAMETER OF
THE OUTDOOR COIL AND OUTDOOR SENSOR:
(
R(0)=15k B(0/100)=3450
)
Temperature(
℃
)
Resistance(k)
Voltage(V)
Temperature(
℃
)
Resistance(k)
Voltage(V)
-20
38.757
0.58143512
31
4.292
2.715076661
-19
36.844
0.60795346
32
4.137
2.76063657
-18
35.038
0.63530819
33
3.989
2.805589174
-17
33.331
0.66352684
34
3.847
2.850117358
-16
31.719
0.69257720
35
3.711
2.894109636
-15
30.196
0.72246147
36
3.58
2.937788018
-14
28.755
0.75321223
37
3.455
2.980713033