25
△
Choose a place as cool as possible.
△
Choose a place that is well ventilated.
△
Allow enough room around the unit for air intake or exhaust and possible maintenance. (see a1,
b1 & c1)
△
Provide a solid base (level concrete pad, concrete block, 10 × 40 cm beams or equal), a minimum
of 10 cm above ground level to reduce humidity and protect the unit against possible water damage
and decreased service life.
△
Install cushion rubber under unit’s feet to reduce vibration and noise.
△
Use lug bolts or equal to bolt down unit, reducing vibration and noise.
a1
b1
c1
Recommended Wire Diameter:
Capacity size
Wire Diameter(mm
2
)
Fuse or Circuit Breaker Capacity
5K~12k
1.0(Power wire)/1.0
(
Connect wire
)
3.15A
(
indoor
)
/15A
(
outdoor
)
18k
2.5(Power wire)/1.5
(
Connect wire
)
3.15A
(
indoor
)
/20A
(
outdoor
)
22K~30K
2.5(Power wire)/2.5
(
Connect wire
)
3.15A
(
indoor
)
/30A
(
outdoor
)