Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
87
00537
(0x0218)
Allow calibration
0: Disallow 1: Allow
R/W
0
00641~00646
(0x0280~0x0285)
CH0~CH5 Out of range
0: normal 1: out of range
R
0
Holding Register( 4xxxx) / Input Register(3xxxx)
Address
Function
R/W
Initial
Value
30513~30518
40513~40518
(0x0200~0x0205)
AI CH0 ~ CH5 Value
R
-
40577~40582
(0x0240~0x0245)
Temperature Compensation
unit: 0.01
℃
, Range: -50.0
℃
~ 50.0
℃
R/W
0x0000
40705~40710
(0x02C0~0x02C5)
CH0~CH5 Input signal type
R/W
0x0401
40737
(0x02E0)
AI Result format of measurement
0x0000: Hex 0x0001: Engineering
R/W
0x0000
40577
(0x02F4)
CH0~CH5 Calibrate maximum value to
each channel. (Each bit map to
corresponding channel)
Ex. Bit 0 = 1, Calibrate CH0.
Bit 1 = 1, Calibrate CH1.
W
0x0000
40578
(0x02F5)
CH0~CH5 Calibrate 0 level to each
channel. (Each bit map to corresponding
channel)
W
0x0000
40579
(0x02F6)
CH0~CH5 Perform internal calibration
to each channel. (Each bit map to
corresponding channel)
W
0x0000
40580
(0x02F7)
CH0~CH5 Calibration in process (Each
bit map to corresponding channel)
0: No operation
1: Calibration in process
R
-
44097
0x1000
Firmware version 2 Bytes
High Byte
Low Byte
Main version
Sub-version
R
-
44098~44105
(0x1001~0x1008)
Module name 16 Bytes (16 ASCII char)
R
-
44106
(0x1009)
Modbus response delay time (unit: ms)
Range: 0~30
R/W
0
Содержание Wolf Series RS-485
Страница 1: ...Wolf series Remote IO Modules User s Manual ...
Страница 40: ...Wolf Series RS 485 Remote I O Module Wolf series Remote IO Module User s Manual 32 3 2 W M1B102 Coming Soon ...
Страница 81: ...Wolf Series RS 485 Remote I O Module Wolf series Remote IO Module User s Manual 73 3 7 3 Channel Connecting ...