
Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual 100
When Input Active Value Define as 1:
External signal:
Inactivate is 1
Activated is 0
4.2.5.2 Digital Input Status
Following Modbus address can be used to read digital input channel status:
Address
Function
R/W
Initial Value
00001~00032
10001~10032
(0x0000~0x001F)
DI CH0~CH31 Input Status
R
All 0
4.2.5.3 Read/Clear the Digital Input Counter
Module has the function of counting the external pulse number of the digital
signal. The maximum frequency must be less than 100Hz. Following Modbus address
can be used to read or clear current counter.
Address
Function
R/W Initial Value
000145~000176
(0x0090~0x00AF)
DI CH0~CH31 Counter Clear
W
All 0
30001~30032
40001~40032
(0x0000~0x001F)
DI CH0~CH31 DI Counter Value
R
All 0x0000
40137
(0x0088)
DI CH0~CH31 Counter Edge Define
(Each bit map to corresponding
channel)
1=rising edge 0=falling edge
R/W 0x0000
Содержание Wolf Series RS-485
Страница 1: ...Wolf series Remote IO Modules User s Manual ...
Страница 40: ...Wolf Series RS 485 Remote I O Module Wolf series Remote IO Module User s Manual 32 3 2 W M1B102 Coming Soon ...
Страница 81: ...Wolf Series RS 485 Remote I O Module Wolf series Remote IO Module User s Manual 73 3 7 3 Channel Connecting ...