Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
59
44107
(0x100A)
COM port setting: 2bytes
High Byte
Low Byte
0x00: 8-N-1
0x01: 8-N-2
0x02: 8-E-1
0x03: 8-O-1
0x03: 1.2K
0x04: 2.4K
0x05: 4.8K
0x06: 9.6K
0x07: 19.2K
0x08: 38.4K
0x09: 57.6K
0x0A: 115.2K
R/W
0x0006
44108
(0x100B)
Watch dog timer (unit: 0.1s)
Range: 0 ~ 0x00FF
R/W
0x0000
44109
(0x100C)
System watch dog
0x0001: Enable 0x0000: Disable
R/W
0x0000
44110
(0x100D)
Status of system watch dog
0x0001: Timeout 0x0000: Normal
R/W
-
44111
(0x100E)
Counter of communication frame
R
0x0000
3.5.6.2 W-M1B108 Modbus address table
Coil (0xxxx) / (1xxxx)
Address
Function
R/W
Initial
Value
00524
(0x020B)
CJC Enable
0: Disable 1: Enable
R/W
0
00537
(0x0218)
Allow calibration
0: Disallow 1: Allow
R/W
0
00641~00656
(0x0280~0x028F)
CH0~CH15 Out of range
0: normal 1: out of range
R
0
Holding Register( 4xxxx) / Input Register(3xxxx)
Address
Function
R/W
Initial
Value
30513~30528
40513~40528
(0x0200~0x020F)
AI CH0 ~ CH15 Value
R
-
40577~40584
Temperature Compensation
R/W
0x0000