1.4 Watchdog
There are module watchdog and system watchdog in Wolf Series module.
Module watchdog is a hardware monitoring the operation status of module, when
working in a harsh/noisy environment and encountering interference, the module can
automatically reset and reboot by itself. The system watchdog is software monitoring
the operation status of system, its purpose is to provide immediate counter-measure
when erroneous network, communication or breakdown occur. Once time-out occurs,
the module will reset all outputs to SAFE mode to prevent any improper operations on
the controlled target.
Watchdog of Modbus functions as following table~
Address
Function
R/W
Initial value
44108
(0x100B)
Timeout value(0.1s)
Range: 0 ~ 0x00FF
R/W
0x0000
44109
(0x100C)
Function enable/disable
0x0001: Enable
0x0000: Disable
R/W
0x0000
44110
(0x100D)
Watchdog status
0x0001: Timeout
0x0000: Normal
R/W
0x0000
Module watchdog: If discontinuation exceeds 1.6 sec (default), the system would
reset the signal and reboot.
System watchdog: System watchdog is time programmable. When system
watchdog is enabled and module doesn’t receive polling from the host at the time set,
system watchdog time-out will automatically start. Outputs mode is configurable on
certain modules. Please refer to Chapter 3 & Chapter4.