Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
77
40737
(0x02E0)
AI Result format of measurement
0x0000: Hex 0x0001: Engineering
R/W
0x0000
40577
(0x02F4)
CH0~CH7 Calibrate maximum value to
each channel. (Each bit map to
corresponding channel)
Ex. Bit 0 = 1, Calibrate CH0.
Bit 1 = 1, Calibrate CH1.
W
0x0000
40578
(0x02F5)
CH0~CH7 Calibrate 0 level to each
channel. (Each bit map to corresponding
channel)
W
0x0000
40579
(0x02F6)
CH0~CH7 Perform internal calibration
to each channel. (Each bit map to
corresponding channel)
W
0x0000
40580
(0x02F7)
CH0~CH7 Calibration in process (Each
bit map to corresponding channel)
0: No operation
1: Calibration in process
R
-
44097
0x1000
Firmware version 2 Bytes
High Byte
Low Byte
Main version
Sub-version
R
-
44098~44105
(0x1001~0x1008)
Module name 16 Bytes (16 ASCII char)
R
-
44106
(0x1009)
Modbus response delay time (unit: ms)
Range: 0~30
R/W
0
44107
(0x100A)
COM port setting: 2bytes
High Byte
Low Byte
0x00: 8-N-1
0x01: 8-N-2
0x02: 8-E-1
0x03: 8-O-1
0x03: 1.2K
0x04: 2.4K
0x05: 4.8K
0x06: 9.6K
0x07: 19.2K
0x08: 38.4K
0x09: 57.6K
0x0A: 115.2K
R/W
0x0006
44108
(0x100B)
Watch dog timer (unit: 0.1s)
Range: 0 ~ 0x00FF
R/W
0x0000
44109
(0x100C)
System watch dog
0x0001: Enable 0x0000: Disable
R/W
0x0000
Содержание Wolf Series RS-485
Страница 1: ...Wolf series Remote IO Modules User s Manual ...
Страница 40: ...Wolf Series RS 485 Remote I O Module Wolf series Remote IO Module User s Manual 32 3 2 W M1B102 Coming Soon ...
Страница 81: ...Wolf Series RS 485 Remote I O Module Wolf series Remote IO Module User s Manual 73 3 7 3 Channel Connecting ...