Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
66
Value
Input range
Initial value
Current Input
0x0201
4~20mA
◎
0x0202
0~20 mA
0x0203
± 20 mA
3.6.5.2 Hexadecimal / Engineering Unit
Setup the output value on Hexadecimal, or customer scaling. Modbus command
is shown below.
Address
Function
R/W
Initial value
40737
(0x02E0)
AI Value format
0x0000: Hex 0x0001: Engineering
R/W
0x0000
30513~30528
40513~40528
(0x0200~0x020F)
AI CH0 ~ CH7 Value
R
-
Hex Unit data range:
Value
Range
Min. value
Max. value
Current Input
0x0201
4~20mA
0 (0)
FFFF (65535)
0x0202
0~20 mA
0 (0)
FFFF (65535)
0x0203
± 20 mA
8000 (-32768)
7FFF (32767)
Engineering Unit data range:
Value
Range
Min. value
Max. value
Current Input
0x0201
4~20mA
4000
20000
0x0202
0~20 mA
0
20000
0x0203
± 20 mA
-20000
20000
3.6.5.3 Signal Value
Once completing the setup, please enter the measured value. This is to enable/
disable the channel(s) and check if the value is out-of-range (4~20mA contact loss is
deemed to be “out of range”). Modbus command as following: