Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
22
2.1.9 Setup Utility
Wolf series module could be configured via setup utility directly on the PC
workstation equipped with RS-485. Or, use a RS-232 port through RS-485 converter,
USB to RS-485 converter. Utility and setup guideline could be obtained from Advanio
website.
2.1.10 Communication Setup
To setup Wolf series module, MODBUS node address should be determined first.
The factory default to the node address of Wolf M1B series module is 01. The
node address could be setup by two hexadecimal coded rotary switches. The range of
node address is from 0x01 to 0xF7 (1 to 247).
Label
Plastic film