This setup should turn off the power, then use a screwdriver to rotate the rotary
switches, when complete the setup and power on module then the node address should
be determined.
The factory default setting of RS-485 on Wolf series module is 9600bpsN,8,1.
The frame format and baud rate could be changed via utility or MODBUS
command. The baud rate range is from 1200bps to 115.2Kbps. Even and Odd parity
check. The setup utility could be downloaded via Advanio official website, set up
MODBUS command of RS-485 as the following:
Address
Function
R/W Initial value
44107
(0x100A)
Com port parameter :
2 bytes
High Byte
Low Byte
0x00: 8-N-1
0x01: 8-N-2
0x02: 8-E-1
0x03: 8-O-1
0x03:1.2K
0x04:2.4K
0x05:4.8K
0x06:9.6K
0x07:19.2K
0x08:38.4K
0x09:57.6K
0x0A:115.2K
R/W 0x0006