Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
2
1.2 System Specification
Power Requirement
10 ~ 60 VDC
Watchdog Timer
System (1.6 second Fixed)
Communication (Programmable)
Connector
Plug-in-terminal block
(#16~30 AWG)
Temperature (Operating)
-25 ~ 70
℃
Humidity
5 ~ 95 %RH
Temperature (Storage)
-30 ~ 75
℃
Interface
RS-485
Isolation Protection
3000 VDC
Communication Protocol
Modbus RTU
Communication Speed
Serial: From 1200 to 115.2k bps
Communication Distance
Serial: 1.2km
1.3 Set Up and Use
The rotary switch provided by Wolf series module is a handy gadget for user to
facilitate the address setup during the installation Utility software is employed to set
up the module configuration parameter. The factory default can be reset by pressing
INIT for at least 3 second. Furthermore, EEPROM built in the modules is detachable
and can be changed on new module to retain the setting.
For the module installation and system settings in details, please refer to Chapter
2,, for the module details information please refer to Chapter 3 & Chapter 4, for the
frequently asked questions, please refer to Chapter 5 for the technical support, please
refer to Chapter 6.