Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
56
30513~30528
40513~40528
(0x0200~0x020F)
AI CH0 ~ CH15 Value
R
-
Hex Unit data range:
Value
Range
Min. value
Max. value
Thermocouple Input
0x0301
Type J Thermocouple -210 ~ 1200 °C
E999 (-5735)
7FFF (32767)
0x0302
Type K Thermocouple -270 ~ 1372 °C
E6CF (-6449)
7FFF (32767)
0x0303 Type T Thermocouple -270 ~ 400 °C
A99A (-22118)
7FFF (32767)
0x0304 Type E Thermocouple -270 ~ 1000 °C
DD70 (-8848)
7FFF (32767)
0x0305 Type R Thermocouple -50 ~ 1768 °C
FC61 (-927)
7FFF (32767)
0x0306
Type S Thermocouple -50 ~ 1768 °C
FC61 (-927)
7FFF (32767)
0x0307 Type B Thermocouple 0 ~ 1820 °C
0 (0)
7FFF (32767)
0x0308
Type N Thermocouple -270 ~ 1300 °C
E56A (-6806)
7FFF (32767)
Engineering Unit data range:
Value
Range
Min. value
Max. value
Thermocouple Input
0x0301
Type J Thermocouple -210 ~ 1200 °C
-2100
12000
0x0302
Type K Thermocouple -270 ~ 1372 °C
-2700
13720
0x0303 Type T Thermocouple -270 ~ 400 °C
-2700
4000
0x0304 Type E Thermocouple -270 ~ 1000 °C
-2700
10000
0x0305 Type R Thermocouple -50 ~ 1768 °C
-500
17680
0x0306
Type S Thermocouple -50 ~ 1768 °C
-500
17680
0x0307 Type B Thermocouple 0 ~ 1820 °C
0
18200
0x0308
Type N Thermocouple -270 ~ 1300 °C
-270
13000
3.5.5.4 Signal Value
Once completing the setup, please enter the measured value. This is to enable/
disable the channel(s) and check if the value is out-of-range (valtage, 4~20mA or
thermocouple contact loss is deemed to be “out of range”). Modbus command as
following:
Address
Function
R/W Initial Value
40737
(0x02E0)
AI Value format
0x0000: Hex 0x0001: Engineering
R/W
0x0000