
Wolf Series RS-485 Remote I/O Module
Wolf series Remote IO Module User's Manual
83
3.8.5 Related Reference
3.8.5.1 Input Signal Type Setup
Each channel of the module can be indpendently set various analog signal input
range. Modbus command is shown below.
Address
Function
R/W
Initial value
40705~40710
(0x02C0~0x02C5)
CH0~CH5 Input signal type setup
R/W
0x0401
Signals detect range:
Value
Input range
Initial value
Resistance Input
0x0401
Platinum 100 α= 0.00385(IEC); -200 ~ 600 °C
(18.52Ω~ 313.71 Ω)
◎
0x0402
Platinum 100α= 0.00392(JIS); -200 ~ 600 °C
(17.08Ω~ 317.59 Ω)
0x0403
Platinum 1000α=0.00385; -200 ~ 600 °C
(185.2Ω~ 3137.1 Ω)
0x0404
Cu 100@0°Cα=0.00421; -20 ~ 150 °C
(91.564Ω~ 163.168 Ω)
0x0405
Cu 1000@0°Cα=0.00421; -20 ~ 150 °C
(915.64Ω~ 1631.68 Ω)
0x0406
Cu 100@25°Cα=0.00427; 0 ~ 200 °C
(90.346Ω~ 167.750 Ω)
0x0407
Cu 50@0°C; -50 ~ 150 °C
(39.242Ω~ 82.134 Ω)
0x0408
Nickel 100Ωα=0.00618; -60 ~ 180 °C
(69.520Ω ~ 223.221Ω)
0x0409
Nickel 120Ωα=0.00672; -80 ~ 260 °C
(66.60Ω~ 380.31 Ω)
0x040A
Nickel 507.5Ωα=0.00520
;
-80 ~ 260 °C
(344.10Ω~ 1328.16 Ω)
0x040B
Nickel604Ωα=0.00518
;
-200 ~ 200 °C
(245.34Ω~ 1301.9 Ω)
0x040C
BALCO 500
;
-40 ~ 150 °C
(379.35Ω~ 802.36 Ω)
Содержание Wolf Series RS-485
Страница 1: ...Wolf series Remote IO Modules User s Manual ...
Страница 40: ...Wolf Series RS 485 Remote I O Module Wolf series Remote IO Module User s Manual 32 3 2 W M1B102 Coming Soon ...
Страница 81: ...Wolf Series RS 485 Remote I O Module Wolf series Remote IO Module User s Manual 73 3 7 3 Channel Connecting ...