6.15. Codereset
If the installer and/or administrator code gets lost, it is possible to
execute a code reset. In this way all user settings (also programmed
telecommands) will be deleted and the factory defaults for installer
and user codes are reset. All programmed settings in the installer menu
will remain and will not be deleted or reset.
The factory default for the installer code is
7890
The factory default for the administrator code is
1234
7. Explanation of terms
Before starting to program the alarm station, you should understand
the terms used. An explanation of zone types and their attributes.
NOT USED
Program a zone for which no radio detector has been trained or to
whose input no detector has been wired and is therefore no noted as a
Not Used
zone type.
NORMAL ALARM
If the alarm panel is active, this zone immediately triggers an alarm if a
radio detector sends a change to the radio alarm panel or if the state
of the alarm zone changes (e.g., opening the alarm contact).
ENTRY ROUTE
This zone triggers no alarm if an entry/exit zone has previously activated
the entry delay time. An immediate alarm is triggered if no entry delay
is first activated. You can use this zone type for a motion sensor in the
entrance hall pointing to the entry door (fitted with a door contact).
This detector can be used as an entry/exit detector for internal
activation. This zone can be opened when you exit the installer menu.
FINAL EXIT
If the burglar alarm panel is active, this zone first triggers an alarm
following a specified delay time (entry delay). This zone type can be
used for the door contact of your entrance. When you leave the
premises, closing this zone can also be used for ending the exit delay.
24 HOUR
This zone always triggers an immediate alarm. If the alarm panel is
deactivated, the alarm is first heard via the integrated buzzer in the
station. In an active state, the siren output is also activated. If a 24-hour
zone is locked, this applies to the deactivated state only.
1.
Remove power from the panel
(Mains and battery power supply
needs to be removed)
2.
Short cut he code reset jumper
3.
Reapply mains to the panel
4.
Open the code reset jumper