Table 5.1.14.1.-5
Mapping of Modbus data: user-defined registers
Description
HR/IR address
(.bit)
DI/Coil bit
address
Writeable
Value range Comment
UDR 1
1 or 385
UDR 2
2 or 386
UDR 3
3 or 387
UDR 4
4 or 388
UDR 5
5 or 389
UDR 6
6 or 390
UDR 7
7 or 391
UDR 8
8 or 392
UDR 9
9 or 393
UDR 10
10 or 394
UDR 11
11 or 395
UDR 12
12 or 396
UDR 13
13 or 397
UDR 14
14 or 398
UDR 15
15 or 399
UDR 16
16 or 400
Table 5.1.14.1.-6
Mapping of Modbus data: status registers
Description
HR/IR address
(.bit)
DI/Coil bit
address
Writeable
Value range Comment
Status register 1
401
IRF code
See Structure 1
Status register 2
402
Warning
codes
See Structure 1
Status register 3
403
See Structure 1
Table 5.1.14.1.-7
Mapping of Modbus data: analog data
Description
HR/IR address
(.bit)
DI/Coil bit
address
Writeable
Value range Comment
Phase current I
a
x I
n
(CT)
404
0...5000
0...50 x FLA
Phase current I
b
x I
n
(CT)
405
0...5000
0...50 x FLA
Phase current I
c
x I
n
(CT)
406
0...5000
0...50 x FLA
Ground-fault current x I
n
(CT)
407
0...8000
0...800.0% I
n
(CT)
NPS current
408
0...5000
0...50 x FLA
Temperature from RTD1
409
-40...999
°C (signed)
a)
Temperature from RTD2
410
-40...999
°C (signed)
a)
Temperature from RTD3
411
-40...999
°C (signed)
a)
Temperature from RTD4
412
-40...999
°C (signed)
a)
Temperature from RTD5
413
-40...999
°C (signed)
a)
Temperature from RTD6
414
-40...999
°C (signed)
a)
Thermistor 1, resistance value
415
0...200
0...20.0 k
Ω
b)
Thermistor 2, resistance value
416
0...200
0...20.0 k
Ω
b)
82
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version