151
Description
Parameter
(channel 0)
Setting range
Default
setting
Customer
’
s
setting
Sensor/thermistor selection
for input RTD1
V121
0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
8 = PTC 0...20 k
Ω
0
Sensor selection for input
RTD2
V122
0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
0
Sensor selection for input
RTD3
V123
0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
0
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537