Table 5.1.15.1.-7
Event codes E27...E38
Channel
Event
Description
Weighting
factor
Default
value
1
E27
a)
Pickup signal from element 51N activated
1
1
1
E28
a)
Pickup signal from element 51N reset
2
0
1
E29
Trip signal from element 51N activated
4
1
1
E30
Trip signal from element 51N reset
8
0
1
E31
a)
Pickup signal from element 46 activated
16
1
1
E32
a)
Pickup signal from element 46 reset
32
0
1
E33
Trip signal from element 46 activated
64
1
1
E34
Trip signal from element 46 reset
128
0
1
E35
Trip signal from element 46R activated
256
1
1
E36
Trip signal from element 46R reset
512
0
1
E37
CBFAIL activated
1024
0
1
E38
CBFAIL reset
2048
0
Default value of event mask 1V157
341
a)
The event code is not generated during motor start up.
Channel 2
Table 5.1.15.1.-8
Event codes E1...E10
Channel
Event
Description
Weighting
factor
Default
value
2
E1
PO1 activated
1
1
2
E2
PO1 reset
2
1
2
E3
PO2 activated
4
0
2
E4
PO2 reset
8
0
2
E5
PO3 activated
16
0
2
E6
PO3 reset
32
0
2
E7
SO1 activated
64
0
2
E8
SO1 reset
128
0
2
E9
SO2 activated
256
0
2
E10
SO2 reset
512
0
Default value of event mask 2V155
3
Table 5.1.15.1.-9
Event codes E11...E20
Channel
Event
Description
Weighting
factor
Default
value
2
E11
DI1 activated
1
0
2
E12
DI1 deactivated
2
0
2
E13
DI2 activated
4
0
2
E14
DI2 deactivated
8
0
2
E15
DI3 activated
16
0
2
E16
DI3 deactivated
32
0
2
E17
DI4 activated
64
0
2
E18
DI4 deactivated
128
0
106
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version