Table 5.2.3.-4
Measuring range
Measured currents on phases I
a
, I
b
and I
c
as
multiples of the rated currents of the energizing
inputs
0...50
×
I
n
(CT)
Ground-fault current as a multiple of the rated
current of the energizing input
0...8
×
I
n
(CT)
Table 5.2.3.-5
Digital inputs
Rated voltage:
DI1...DI2
DI3...DI5 (optional)
REM610CxxHxxx
110/125/220/250 V DC
Activating threshold
Max. 88 V DC (110 V DC -
20%)
REM610CxxLxxx
24/48/60/110/125/
220/250 V DC
Activating threshold
Max. 19,2 V DC (24 V DC -
20%)
REM610CxxxxMx
24/48/60/110/125/
220/250 V DC
Activating threshold
Max. 19,2 V DC (24 V DC -20%)
Operating range
±
20% of the rated voltage
Current drain
2...18 mA
Power consumption/input
≤
0.9 W
Table 5.2.3.-6
Non-trip output SO1
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Table 5.2.3.-7
Non-trip output SO2 and IRF output
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
10 A
Make and carry for 0.5 s
15 A
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
120
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537
Содержание REM 610
Страница 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 124: ...124 ...
Страница 144: ...144 ...
Страница 154: ...154 ...
Страница 157: ......