When setting values are altered via the front communication port, the relay checks
that the entered parameter values are within the permitted setting range. If an entered
value is too high or too low, the setting value remains unchanged.
The relay has a counter which can be accessed via
CONFIGURATION
\
COMMUNICATION
in the HMI menu. The counter value is set to zero when the
relay receives a valid message.
5.1.13.
IEC 60870-5-103 remote communication protocol
The relay supports the IEC 60870-5-103 remote communication protocol in the
unbalanced transmission mode. The IEC 60870-5-103 protocol is used to transfer
measurand and status data from the slave to the master. However, the IEC 60870-5-
103 protocol cannot be used to transfer disturbance recorder data.
The IEC 60870-5-103 protocol can be used only through the rear connection of the
relay on the optional communication module. Connecting the relay to a fibre-optic
communication bus requires a fibre-optic communication module. The line-idle
state of the fibre-optic communication module can be selected either via the HMI or
the SPA bus. According to the IEC 60870-5-103 standard, the line-idle state is
“
light
on
”
. To ensure communication, the line-idle state should be the same for both the
master and the slave device. The connection topology can be selected to be either
loop or star, the default being loop, and either via the HMI or the SPA bus. The
selected line-idle state and connection topology apply irrespective of which rear
communication protocol is active.
The relay uses the SPA bus protocol as default when the optional communication
module is in use. The protocol selection is memorized and is therefore always
activated when the rear connection is in use. The baud rate can be selected either via
the HMI or the SPA bus. According to the IEC 60870-5-103 standard, the baud rate
is 9.6 kbps. When the IEC 60870-5-103 protocol is active, event masks are not in
use. Consequently, all events in the selected configuration set are included in the
event reporting.
The relay is provided with two different selectable configuration sets, of which
configuration set 1 is used by default.
Configuration set 1 is intended to be used when the optional RTD module is not
installed. Configuration set 2 includes additional information, for example
temperature protection events and digital input events 3...5, provided that the
optional RTD module is installed.
Function type and information number are mapped into configuration sets according
to the IEC 60870-5-103 standard to the extent that these have been defined by the
standard. If not defined by the standard, the type of function and/or the information
number are/is mapped into a private range.
The tables below indicate the information mapping of the corresponding
configuration sets. The column GI indicates whether the status of the specified
information object is transmitted within the general interrogation cycle. The relative
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537
Содержание REM 610
Страница 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 124: ...124 ...
Страница 144: ...144 ...
Страница 154: ...154 ...
Страница 157: ......