Table 5.1.15.1.-1
Event masks
Event mask
Code
Setting range
Default setting
V155
E31...E36
0...63
1
1V155
1E1...1E14
0...16383
4180
1V156
1E15...1E26
0...4095
1365
1V157
1E27...1E38
0...4095
341
2V155
2E1...2E10
0...1023
3
2V156
2E11...2E20
0...1023
0
2V157
2E21...2E28
0...255
0
Channel 0
Events always included in the event reporting:
Table 5.1.15.1.-2
Event codes E1...E7
Channel
Event
Description
0
E1
IRF
0
E2
IRF disappeared
0
E3
Warning
0
E4
Warning disappeared
0
E5
Emergency start activated
0
E6
Emergency start deactivated
0
E7
The thermal level has been changed via serial communication
Table 5.1.15.1.-3
Event codes E50...E51
Channel
Event
Description
0
E50
Relay restart
0
E51
Event buffer overflow
Events possible to mask out:
Table 5.1.15.1.-4
Event codes E31...E36
Channel
Event
Description
Weighting
factor
Default
value
0
E31
Disturbance recorder triggered
1
1
0
E32
Disturbance recorder memory cleared
2
0
0
E33
HMI Setting password opened
4
0
0
E34
HMI Setting password closed
8
0
0
E35
HMI Communication password opened
16
0
0
E36
HMI Communication password closed
32
0
Default value of event mask V155
1
104
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537
Содержание REM 610
Страница 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 124: ...124 ...
Страница 144: ...144 ...
Страница 154: ...154 ...
Страница 157: ......