Description
Parameter
(channel 0)
Setting range
Default
setting
Customer
’
s
setting
Sensor/thermistor selection
for input RTD4
V124
0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
8 = PTC 0...20 k
Ω
0
Sensor selection for input
RTD5
V125
0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
0
Sensor selection for input
RTD6
V126
0 = not in use
1 = Pt100 -45...
+150°C
2 = Pt250 -45...
+150°C
3 = Pt1000 -45...
+150°C
4 = Ni100 -45...
+250°C
5 = Ni120 -45...
+250°C
6 = Cu10 -45...
+150°C
7 = Ni120US -45...
+250°C
Remote control of settings
V150
0 = setting group 1
1 = setting group 2
0
Unit address of the relay
V200
1...254
1
Data transfer rate (SPA),
kbps
V201
9.6/4.8
9.6
152
REM 610
REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537
Содержание REM 610
Страница 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 124: ...124 ...
Страница 144: ...144 ...
Страница 154: ...154 ...
Страница 157: ......