123
Table 5.2.3.-13
Standard tests
Insulation tests:
Dielectric tests
According to IEC 60255-5
*
Test voltage
2 kV, 50 Hz, 1 min
Impulse voltage test
According to IEC 60255-5
*
Test voltage
5 kV, unipolar impulses, waveform
1.2/50
μ
s, source energy 0.5 J
Insulation resistance measurements
According to IEC 60255-5
*
Isolation resistance
>100 M
Ω
, 500 V DC
Mechanical tests:
Vibration tests (sinusoidal)
According to IEC 60255-21-1, class I
Shock and bump test
According to IEC 60255-21-2, class I
Table 5.2.3.-14
Data communication
Rear interface:
*
Fibre-optic or RS-485 connection
*
SPA bus, IEC 60870-5-103, DNP 3.0 or Modbus protocol
*
9.6 or 4.8 kbps (additionally 2.4, 1.2 or 0.3 kbps for Modbus)
Front interface:
*
Optical connection (infrared): wirelessly or via the front communication cable
(1MRS050698)
*
SPA bus protocol
*
9.6 or 4.8 kbps (9.6 kbps with front communication cable)
Optional communication modules and protocols
*
SPA-bus, IEC 60870-5-103, Modbus® (RTU and ASCII):
*
Plastic fibre
*
Plastic and glass fibre
*
RS485
Auxiliary voltage
The relay requires a secured auxiliary voltage supply to operate. The internal power
supply of the relay forms the voltages required by the relay electronics. The power
supply is a galvanically isolated (flyback-type) DC/DC converter. When the
auxiliary voltage is connected, the green target LED (ready) on the front panel is lit.
For detailed information on power supply, refer to Table 5.2.3.-2.
The primary side of the power supply is protected with a fuse located on the printed
circuit board of the relay.
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537
Содержание REM 610
Страница 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 124: ...124 ...
Страница 144: ...144 ...
Страница 154: ...154 ...
Страница 157: ......