![ABB REM 610 Скачать руководство пользователя страница 83](http://html.mh-extra.com/html/abb/rem-610/rem-610_technical-reference-manual_4631083.webp)
83
Table footnotes from previous page
a)
If the input is out of operation or the optional RTD module has not been installed, the value -32768 will be returned.
b)
If the input is out of operation or the optional RTD module has not been installed, the value 655 will be returned.
Table 5.1.14.1.-8
Mapping of Modbus data: digital data
Description
HR/IR address
(.bit)
DI/Coil bit
address
Writeable
Value range Comment
Motor start up
417.00
1
0/1
1 = begins
0 = ends
Motor start up CD
417.01
2
Pickup signal from element 49
417.02
3
0/1
1 = activated
Pickup signal from element 49 CD
417.03
4
Alarm signal from element 49
417.04
5
0/1
1 = activated
Alarm signal from element 49 CD
417.05
6
Trip signal from element 49
417.06
7
0/1
1 = activated
Trip signal from element 49 CD
417.07
8
Restart disable signal from element 49
417.08
9
0/1
1 = activated
Restart disable signal from element 49
CD
417.09
10
Restart disable signal from element 66
417.10
11
0/1
1 = activated
Restart disable signal from element 66
CD
417.11
12
Restart disable
417.12
13
0/1
1 = activated
a)
Restart disable CD
417.13
14
Pickup signal from element (48/14
PICKUP)
2
x (48/14 TDLY) or 48/14
417.14
15
0/1
1 = activated
Pickup signal from element (48/14
PICKUP)
2
x (48/14 TDLY) or 48/14 CD
417.15
16
Trip signal from element (48/14
PICKUP)
2
x (48/14 TDLY) or 48/14
418.00
17
0/1
1 = activated
Trip signal from element (48/14
PICKUP)
2
x (48/14 TDLY) or 48/14 CD
418.01
18
Pickup signal from element 50P-1
418.02
19
0/1
1 = activated
Pickup signal from element 50P-1 CD
418.03
20
Trip signal from element 50P-1
418.04
21
0/1
1 = activated
Trip signal from element 50P-1 CD
418.05
22
Pickup signal from element 37
418.06
23
0/1
1 = activated
Pickup signal from element 37 CD
418.07
24
Trip signal from element 37
418.08
25
0/1
1 = activated
Trip signal from element 37 CD
418.09
26
Pickup signal from element 51N
418.10
27
0/1
1 = activated
Pickup signal from element 51N CD
418.11
28
Trip signal from element 51N
418.12
29
0/1
1 = activated
Trip signal from element 51N CD
418.13
30
Pickup signal from element 46
418.14
31
0/1
1 = activated
Pickup signal from element 46 CD
418.15
32
Trip signal from element 46
419.00
33
0/1
1 = activated
Motor Protection Relay
Technical Reference Manual - ANSI Version
REM 610
REM 610
1MRS755537
Содержание REM 610
Страница 1: ...Motor Protection Relay REM 610 REM 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 124: ...124 ...
Страница 144: ...144 ...
Страница 154: ...154 ...
Страница 157: ......