1MRS 752264-MUM
Motor Protection Relay
Operator’s Manual
REM 610
27
Fig. 3.2.2.3.-2 Configuration, part 2
3.2.2.4.
How to acknowledge and reset indications, output contacts and
memorized values
• To clear the LEDs and the display, press
. The LEDs and the display will be
cleared only if the fault has disappeared.
• Press
for at least five seconds to unlatch the output contacts. Note that the
LEDs and the display have to be cleared before this.
• Press
and
simultaneously for at least half a second to perform a master
reset, i.e. to clear indications and memorized values and to unlatch the output
contacts. The display being inverted confirms this action. Memorized values
include recorded data, disturbance recorder data and average values (demand
values and history data, except for the running time).
Config2REM610_b
NOT IN USE
Pt-100 -45..150
PASSWORD HMI
TIME
TRIP CIRCUIT SUP
Main Menu
Group Menu
Parameter Menus
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
CONFIGURATION
FREQUENCY :60
CONFIGURATION
FREQUENCY :50
FREQUENCY
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
MEMORY SETTINGS
PASSWORD HMI :xxx
CONFIGURATION
hh.mm;ss
CONFIGURATION
YY-MM-DD
CONFIGURATION
NOT IN USE
Pt100 -45..150
Pt250 -45..150
Pt1000 -45..150
Ni100 -45..250
Ni120 -45..250
RTD INPUTS
TCS ENABLED
CONFIGURATION
CH 1 RTD/TH
CH 2 RTD
CH 3 RTD
CH 4 RTD/TH
CH 5 RTD
CH 6 RTD
TCS DISABLED
Cu10 -45..150
Ni120US -45..250
PTC 0..20k
W
CONFIGURATION
Pt250 -45..150
Pt1000 -45..150
Ni100 -45..250
Ni120 -45..250
Cu10 -45..150
Ni120US -45..250
CONFIGURATION
NOT IN USE
Pt-100 -45..150
Pt250 -45..150
Pt1000 -45..150
Ni100 -45..250
Ni120 -45..250
Cu10 -45..150
Ni120US -45..250
PTC 0..20k
W
CONFIGURATION
NOT IN USE
Pt-100 -45..150
Pt250 -45..150
Pt1000 -45..150
Ni100 -45..250
Ni120 -45..250
Cu10 -45..150
Ni120US -45..250
INFO