![ABB REM 610 Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/abb/rem-610/rem-610_operators-manual_3428235034.webp)
34
1MRS 752264-MUM
Motor Protection Relay
Operator’s Manual
REM 610
1)
Temperature protection stages are out of operation.
Trip-circuit
supervision
2
• Error in trip circuit
- Check the trip circuit for broken conductors and correct.
- Warning will not be displayed if trip-circuit supervision (TCS)
has been disabled
Power supply
module
temperature high
4
• Temperature inside relay is too high
- Check that ambient temperature is within service temperature
range
Communication
module faulty or
missing
8
• Communication module faulty or not installed
- Check that plug-in unit is properly attached to relay case
- Check that communication module is installed
- Warning will not be displayed if rear communication module
has been disabled
- In case only this warning is active, it will be displayed in text
format (Comm.card faulty)
RTD module
faulty
16
Three possible causes:
1) Storing in non-volatile memory has not been successful, which
means that old settings will be taken into use after power up
2) Self calibration has failed
3) Offset voltage out of range
- If warning is not cleared after a power reset, the relay may
require service
Temperature
sensor range
error
32
• At least one sensor (RTD1...6) is outside measurement range
- Check that sensors are not broken
Sensor circuit
open or shorted
(RTD1)
64
• Circuit is open or shorted
1)
- Check wiring of sensor
- Check that sensor is not broken
Sensor circuit
open or shorted
(RTD2)
128
• Circuit is open or shorted
1)
- Check wiring of sensor
- Check that sensor is not broken
Sensor circuit
open or shorted
(RTD3)
256
• Circuit is open or shorted
1)
- Check wiring of sensor
- Check that sensor is not broken
Sensor circuit
open or shorted
(RTD4)
512
• Circuit is open or shorted
1)
- Check wiring of sensor
- Check that sensor is not broken
Sensor circuit
open or shorted
(RTD5)
1024
• Circuit is open or shorted
1)
- Check wiring of sensor
- Check that sensor is not broken
Sensor circuit
open or shorted
(RTD6)
2048
• Circuit is open or shorted
1)
- Check wiring of sensor
- Check that sensor is not broken
Thermistor circuit
open or shorted
(Thermistor1)
4096
• Circuit is open or shorted
- Check wiring of thermistor
- Check that thermistor is not broken
Thermistor circuit
open or shorted
(Thermistor2)
8192
• Circuit is open or shorted
- Check wiring of thermistor
- Check that thermistor is not broken
Σ
:
16383
Table 3.3.2.3-2
Warning codes