1MRS 752264-MUM
Motor Protection Relay
Operator’s Manual
REM 610
13
As soon as you have replaced the default HMI password, the new password will be
required for altering parameter values. Once you have given the valid password, the
display will remain in the setting mode until returned to the idle mode.
Fig. 3.1.6.-1
Password request for editing setting parameters
Change the HMI password as follows:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select
CONFIGURATION\PASSWORD HMI
and press
.
3. Press
to enter the setting mode and give the current HMI password if
required. If the default password 999 is still valid, no password will be required.
4. The first digit of the password to be edited will start to flash. Set the digit using
and
.
5. Activate the next digit to be set by pressing
or
.
6. To store the new password and return the display to the view mode, press
.
The display will confirm the storage by once flashing “
---
” on the display.
Alternatively, to exit the setting mode without storing the password change,
press
once before confirming and the display will be returned to the view
mode.
7. Press
to return the display to the idle mode.
Fig. 3.1.6.-2
Changing the HMI password
3.1.7.
SPA password
The password for SPA bus communication is required for altering parameter values
via the SPA bus. The default password is 001. You can change the SPA password
either via the HMI or the SPA bus by first entering the currently valid password into
parameter V160 and then entering the new password into parameter V161.
Password_a
PASSWORD :000
SETTINGS
PasswordREM610_b
Main Menu
Group Menu
Parameter Menu
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
PASSWORD HMI
TIME
TRIP CIRCUIT SUP
FREQUENCY
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
MEMORY SETTINGS
PASSWORD HMI :xxx
CONFIGURATION
Scroll for the digit
Set the digit
Confirm
Cancel
RTD INPUTS
INFO