1MRS 752264-MUM
Motor Protection Relay
Operator’s Manual
REM 610
31
indicator LEDs. The text message for the restart inhibit state is non-latching,
whereas the status indication via a programmable LED can be either latching or non-
latching.
The restart of a motor can be inhibited by the thermal protection, the cumulative
start-up time counter or an external digital input signal. For the priority of
indications for the restart inhibit state; refer to section Priority of operation
indication messages.
Fig. 3.3.2.1.-4 Restart inhibit indication
Latching and non-latching indications
A latching operation indication message will remain on the display until manually
cleared or until replaced by a message of higher priority. However, if the fault is
stable and has not disappeared, the operation indication message and the LED(s) will
not be cleared. An operation indication generated by a non-latching start will
automatically be cleared when the stage is reset.
Priority of operation indication messages
The messages on the display have a certain priority order. If different types of
indications are activated simultaneously, the message with the highest priority will
appear on the display.
The priority order of the messages:
1. CBFP
2. Trip
3. Start/Alarm
4. Restart inhibit
4.1. Thermal protection
4.2. Cumulative start-up time counter
4.3. External restart inhibit
When several protection stages generate starts or alarms, the last start/alarm
indication message will be displayed. When several protection stages trip, the first
trip indication message will be displayed until the time, as specified by the
NEW
TRIP IND.
setting value, has expired. After this, a new trip indication message
can displace the old one. A hidden trip indication message can be brought forward
by pressing
.
3.3.2.2.
Disturbance recorder indication
When the display is in the idle mode, an asterisk “
*
” indicating that the disturbance
recorder has been triggered and is ready to be unloaded, will be shown in the lower
right-hand corner of the display.
RestInhIEC_a
tsi
RESTART INHIBIT
S