30
1MRS 752264-MUM
Motor Protection Relay
Operator’s Manual
REM 610
For instructions on setting the switchgroups, refer to section Switchgroups.
3.3.2.
Indication messages
The messages give an overview of protection operations and internal relay faults.
3.3.2.1.
Operation indication messages
When a protection stage starts, the text
START
will appear on the display along with
the name of the function. Additionally, in case of a latching start indication, the
name of the energizing input(s) which caused the fault will be displayed (except for
the motor start-up supervision based on thermal stress calculation and the unbalance
protection). The yellow indicator LED will be lit.
Fig. 3.3.2.1.-1 Latching start indication
When a protection stage trips, the text
TRIP
will appear on the display along with
the name of the function. Additionally, the name of the energizing input(s) which
caused the fault will be displayed (except for the motor start-up supervision, phase
unbalance, phase reversal, thermal overload and temperature protection). The red
indicator will be lit.
Fig. 3.3.2.1.-2 Trip indication
In case of an alarm from the thermal overload or temperature protection, the text
ALARM
will appear on the display along with the function symbol and the yellow
indicator LED will be lit.
Fig. 3.3.2.1.-3 Alarm indication
In case of a restart inhibit state, the text
RESTART INHIBIT
will appear on the
display. The state will not affect the start/alarm and trip LEDs, but instead you can
use a programmable LED to indicate the state; refer to section Programmable
St
artIEC_a
START
I>> L1
TripIEC_a
TRIP
I>> L1/L2
AlarmIEC_a
ALARM
>