All three inputs
GRPxLx
should be connected to SMAI for calculating sequence
components for
ConnectionType
set to
Ph-N
.
•
At least two inputs
GRPxLx
should be connected to SMAI for calculating the
positive and negative sequence component for
ConnectionType
set to
Ph-Ph
.
Calculation of zero sequence requires
GRPxN
input to be connected.
•
Negation setting inverts (reverse) the polarity of the analog input signal. It is
recommended that use of this setting is done with care, mistake in setting may
lead to maloperation of directional functions.
Frequency adaptivity
SMAI function performs DFT calculations for obtaining various electrical
parameters. DFT uses some reference frequency for performing calculations. For
most of the cases, these calculations are done using a fixed DFT reference based on
system frequency. However, if the frequency of the network is expected to vary more
than 2 Hz from the nominal frequency, more accurate DFT results can be obtained if
the adaptive DFT is used. This means that the frequency of the network is tracked and
the DFT calculation is adapted according to that.
DFTRefExtOut
and
DFTReference
need to be set appropriately for adaptive DFT
calculations.
DFTRefExtOut
: Setting valid only for the instance of function block SMAI_20_1. It
decides the reference block for external output
SPFCOUT
.
DFTReference
: Reference DFT for the block. This setting decides DFT reference for
DFT calculations.
DFTReference
set to
InternalDFTRef
uses fixed DFT reference
based on the set system frequency.
DFTReference
set to
DFTRefGrpX
uses DFT
reference from the selected group block, when own group selected adaptive DFT
reference will be used based on the calculated signal frequency from own group.
DFTReference
set to
External DFT Ref
will use reference based on input signal
DFTSPFC
.
Settings
DFTRefExtOut
and
DFTReference
shall be set to default
value
InternalDFTRef
if no VT inputs are available. However, if it is
necessary to use frequency adaptive DFT (
DFTReference
set to other
than default, referring current measuring SMAI) when no voltages are
available, note that the
MinValFreqMeas
setting is still set in
reference to
UBase
(of the selected GBASVAL group). This means
that the minimum level for the current amplitude is based on
UBase
.
For example, if
UBase
is 20000, the resulting minimum amplitude for
current is 20000 * 10% = 2000.
MinValFreqMeas
: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of the voltage in the selected Global Base voltage
group (GBASVAL:n, where 1<n<6).
Section 17
1MRK 502 048-UEN A
Basic IED functions
644
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...