14.17.2
Functionality
The circuit breaker condition monitoring function SSCBR is used to monitor different
parameters of the circuit breaker. The breaker requires maintenance when the number
of operations has reached a predefined value. The energy is calculated from the
measured input currents as a sum of I
y
t values. Alarms are generated when the
calculated values exceed the threshold settings.
The function contains a block alarm functionality.
The supervised and presented breaker functions include
•
breaker open and close travel time
•
spring charging time
•
number of breaker operations
•
accumulated I
Y
t per phase with alarm and lockout
•
remaining breaker life per phase
•
breaker inactivity
14.17.3
Function block
GUID-365D67A9-BEF8-4351-A828-ED650D5A2CAD V1 EN
Figure 264:
SSCBR function block
14.17.4
Signals
Table 428:
SSCBR Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
BLOCK
BOOLEAN
0
Block of function
BLK_ALM
BOOLEAN
0
Block all the alarms
POSOPEN
BOOLEAN
0
Signal for open position of apparatus from I/O
POSCLOSE
BOOLEAN
0
Signal for close position of apparatus from I/O
ALMPRES
BOOLEAN
0
Binary pressure alarm input
Table continues on next page
Section 14
1MRK 502 048-UEN A
Monitoring
560
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...