12.3.4.6
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
12.3.5
Interlocking for bus-section disconnector A1A2_DC
12.3.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for bus-section
disconnector
A1A2_DC
-
3
12.3.5.2
Functionality
The interlocking for bus-section disconnector (A1A2_DC) function is used for one
bus-section disconnector between section 1 and 2 according to figure
. A1A2_DC
function can be used for different busbars, which includes a bus-section disconnector.
WA1 (A1)
WA2 (A2)
QB
QC1
QC2
A1A2_DC
en04000492.vsd
IEC04000492 V1 EN
Figure 185:
Switchyard layout A1A2_DC
1MRK 502 048-UEN A
Section 12
Control
363
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...