Overexcitation M-V/Hz>
Excitation M
M=V/Hz>
IEC09000114 V1 EN
Figure 139:
Restrictions imposed on inverse delays by
A definite maximum time of 1800 seconds is used to limit the operate time at low
degrees of overexcitation of
V/Hz>
. Inverse delays longer than 1800 seconds will not
be allowed. In case the inverse delay is longer than 1800 seconds, OEXPVPH trips
tMax
A definite minimum time
(tMin)
, can be used to limit the operate time at high degrees
of overexcitation for
V/Hz>
. In case the inverse delay is shorter than
tMin
, OEXPVPH
function trips after
tMin
seconds.
1MRK 502 048-UEN A
Section 9
Voltage protection
281