background image

 
 

 

 

 

INSTALLATION, OPERATION AND 

MAINTENANCE MANUAL 

 

AG STOP GATE 

SL STOP LOG

 

 

 

 

 

Содержание AG STOP GATE

Страница 1: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL AG STOP GATE SL STOP LOG...

Страница 2: ...the following Orbinox equipment o AG stop gates o SL stop logs The manual uses AWWA C561 terminology see section 2 Slide gate or gate are also general terms used to refer to all type of equipment Sect...

Страница 3: ...IOM AG SL 2 EQUIPMENT MAIN COMPONENTS ITEM DESCRIPTION 1 FRAME 2 SLIDE FOR AG LOG FOR SL 3 GUIDE 4 LATERAL GUIDE 5 VERTICAL SEAL 6 VERTICAL SEAL RETAINER 7 BOTTOM SEAL 8 BOTTOM SEAL RETAINER Figure 1...

Страница 4: ...Storage Check the equipment on delivery and report back to Orbinox any missing components within 3 days from receipt of the equipment Orbinox will not accept responsibility for loss or damage to any e...

Страница 5: ...specified 4 1 EMBEDDED IN CONCRETE IN THE CHANNEL RECESS Step 1 Initial assessment Check that the concrete wall meets the requirements described in Section 4 Verify that all installation materials spe...

Страница 6: ...Figure 6 Install the bottom anchor bolts and then the lateral anchor bolts see Figure 8 All Face Mounted Channel Gates include lateral mounting Figure 6 Figure 7 brackets For smaller sizes typically...

Страница 7: ...e grout fill is twofold o Fill the voids between the frame frame invert and the channel o Make a smooth transition for water flow CAUTION Make sure not to get grout or any other foreign material on th...

Страница 8: ...lling the hole on the other side make sure the frame is perfectly leveled Step 3 Construction sealant application Remove the unit from the wall first remove the nuts of the anchor bolts Apply construc...

Страница 9: ...e opening width every 1 meter The maximum deviation should be width 1000 o Verify that the frame invert has been embedded in concrete Wall mounted at the end of the channel installation Verify that th...

Страница 10: ...he slide Please refer to section 7 1 for detailed information about the required grease type The following equipment can be used to lift up the gate or logs o Hand pull the slide or logs are equipped...

Страница 11: ...the seals and make sure they are not damaged Seals shall be replaced if damaged see section 7 2 Check tightness of all unit assembly bolts and anchor bolts Spare parts Orbinox does not recommend stock...

Страница 12: ...ront polyethylene guides items 4 and 5 o Remove side seals item 8 and replace it by the new seal o Note 1 Apply glue where the bottom seal and side seals join o Note 2 After installing the new seal ap...

Страница 13: ...l does not meet the required tolerance specification Uninstall unit repair the concrete wall and re install the unit Insufficient construction sealant refer to the GAD Uninstall the unit clean the con...

Страница 14: ...ithin the tolerances defined in DIN 18202 Deviation Maximun deviation Linear deviation DLx DLy DLyy DIN 18202 table 1 group 2 for DLx e DLy DIN 18202 table 1 group 5 for DLyy Angular deviation DAx DAy...

Отзывы: