IOM MANUAL
AG STOP GATE
SL STOP LOGS
www.orbinox.com
EDITION 01/2017
IOM-AG-SL
8.
TROUBLESHOOTING
SYMPTOM
CAUSE
SOLUTION
LEAKAGE (Between frme and
concrete wall, for Face Mounted In
Existing Channel Configuration)
Concrete Wall does not meet the
required tolerance specification
Uninstall unit, repair the concrete
wall and re-install the unit
Gaps between frame and face of
wall due to miss-application of
grout fill
Grout Fill remaining gaps
LEAKAGE (Leakage between frame
and concrete wall, for Wall Mounted
Configuration).
Concrete Wall does not meet the
required tolerance specification
Uninstall unit, repair the concrete
wall and re-install the unit
Insufficient construction sealant
(refer to the GAD)
Uninstall the unit, clean the
concrete wall, and apply new
construction sealant (refer to the
GAD for type and quantity).
Loose anchor bolts
Incorrect anchor bolts (refer to the
GAD)
Tighten anchor bolts
Install appropriate anchor bolts
(refer to the GAD for type and
quantity)
LEAKAGE (through the bottom seal)
Foreign deposits trapped in
between the frame invert and bottom
seal
Open slightly the slide and
remove all foreign deposits. Check
if bottom seal has been damaged.
Damaged bottom seal
Replace bottom seal
EXCESSIVE FORZE REQUIRED FOR
OPERATION
Dry seals
Wet seals