Table 539:
Binary inputs X339, 3U full 19”
Terminal
Description
PCM600 info
Hardware module
instance
Hardware channel
X339-1
- for input 1
BIO_6
BI1
X339-2
Binary input 1 +
BIO_6
BI1
X339-3
-
X339-4
Common - for inputs 2-3
X339-5
Binary input 2 +
BIO_6
BI2
X339-6
Binary input 3 +
BIO_6
BI3
X339-7
-
X339-8
Common - for inputs 4-5
X339-9
Binary input 4 +
BIO_6
BI4
X339-10
Binary input 5 +
BIO_6
BI5
X339-11
-
X339-12
Common - for inputs 6-7
X339-13
Binary input 6 +
BIO_6
BI6
X339-14
Binary input 7 +
BIO_6
BI7
X339-15
-
X339-16
Common - for inputs 8-9
X339-17
Binary input 8 +
BIO_6
BI8
X339-18
Binary input 9 +
BIO_6
BI9
18.3
Outputs
18.3.1
Outputs for tripping, controlling and signalling
Output contacts PO1, PO2 and PO3 are power output contacts used, for example, for
controlling circuit breakers.
Each signal connector terminal is connected with one 0.5...2.5 mm
2
wire or with two
0.5...1.0 mm
2
wires.
The connected DC voltage to outputs with trip circuit supervision
(TCS) must have correct polarity or the trip circuit supervision
TCSSCBR function will not operate properly.
Section 18
1MRK 502 048-UEN A
IED physical connections
664
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...