Functionality
The OR function is used to form general combinatory expressions with boolean
variables. The OR function block has six inputs and two outputs. One of the outputs
is inverted.
Function block
OR
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
IEC09000288-1-en.vsd
IEC09000288 V1 EN
Figure 217:
OR function block
Signals
Table 300:
OR Input signals
Name
Type
Default
Description
INPUT1
BOOLEAN
0
Input signal 1
INPUT2
BOOLEAN
0
Input signal 2
INPUT3
BOOLEAN
0
Input signal 3
INPUT4
BOOLEAN
0
Input signal 4
INPUT5
BOOLEAN
0
Input signal 5
INPUT6
BOOLEAN
0
Input signal 6
Table 301:
OR Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
NOUT
BOOLEAN
Inverted output signal
Settings
The function does not have any parameters available in Local HMI or Protection and
Control IED Manager (PCM600).
13.3.1.3
Inverter function block INVERTER
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Inverter function block
INVERTER
-
-
Section 13
1MRK 502 048-UEN A
Logic
442
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...