7.3.5
Settings
Table 64:
LEXPDIS Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OperationZ1
Off
On
-
-
On
Operation Off/On zone Z1
XoffsetZ1
-1000.00 - 1000.00
%
0.01
-10.00
Offset of Z1 circle top point along X axis in
% of Zbase
Z1diameter
0.01 - 3000.00
%
0.01
100.00
Diameter of imedance circle for Z1 in % of
Zbase
tZ1
0.00 - 6000.00
s
0.01
0.01
Trip time delay for Z1
OperationZ2
Off
On
-
-
On
Operation Off/On zone Z2
XoffsetZ2
-1000.00 - 1000.00
%
0.01
-10.00
Offset of Z2 circle top point along X axis in
% of Zbase
Z2diameter
0.01 - 3000.00
%
0.01
200.00
Diameter of imedance circle for Z2 in % of
Zbase
tZ2
0.00 - 6000.00
s
0.01
1.00
Trip time delay for Z2
Table 65:
LEXPDIS Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
DirSuperv
Off
On
-
-
Off
Operation Off/On for additional directional
criterion
XoffsetDirLine
-1000.00 - 3000.00
%
0.01
0.00
Offset of directional line along X axis in %
of Zbase
DirAngle
-180.0 - 180.0
Deg
0.1
-13.0
Angle between directional line and R-axis
in degrees
Table 66:
LEXPDIS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Table 67:
LEXPDIS Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
InvertCTCurr
No
Yes
-
-
No
Invert current direction
1MRK 502 048-UEN A
Section 7
Impedance protection
155
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...