8.6.4
Signals
Table 115:
CCRPLD Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
BLOCK
BOOLEAN
0
Block of function
CLOSECMD
BOOLEAN
0
Close order to CB
OPENCMD
BOOLEAN
0
Open order to CB
EXTPDIND
BOOLEAN
0
Pole discordance signal from CB logic
Table 116:
CCRPLD Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal to CB
START
BOOLEAN
Trip condition TRUE, waiting for time delay
8.6.5
Settings
Table 117:
CCRPLD Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
tTrip
0.000 - 60.000
s
0.001
0.300
Time delay between trip condition and trip
signal
ContSel
Off
PD signal from CB
-
-
Off
Contact function selection
CurrSel
Off
CB oper monitor
Continuous monitor
-
-
Off
Current function selection
CurrUnsymLevel
0 - 100
%
1
80
Unsym magn of lowest phase current
compared to the highest.
CurrRelLevel
0 - 100
%IB
1
10
Current magnitude for release of the
function in % of IBase
Table 118:
CCRPLD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Section 8
1MRK 502 048-UEN A
Current protection
228
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...