8.3.3
Function block
SDEPSDE
I3P*
U3P*
BLOCK
BLKUN
TRIP
TRDIRIN
TRNDIN
TRUN
START
STDIRIN
STNDIN
STUN
STFW
STRV
STDIR
UNREL
IEC08000036 V1 EN
Figure 99:
SDEPSDE function block
8.3.4
Signals
Table 96:
SDEPSDE Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLKUN
BOOLEAN
0
Blocks the non-directional voltage residual outputs
Table 97:
SDEPSDE Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TRDIRIN
BOOLEAN
Trip of the directional residual overcurrent
TRNDIN
BOOLEAN
Trip of non-directional residual overcurrent
TRUN
BOOLEAN
Trip of non-directional residual overvoltage
START
BOOLEAN
General start signal
STDIRIN
BOOLEAN
Start of the directional residual overcurrent function
STNDIN
BOOLEAN
Start of non directional residual overcurrent
STUN
BOOLEAN
Start of non directional residual overvoltage
STFW
BOOLEAN
Start of directional function for fault in forward
direction
STRV
BOOLEAN
Start of directional function for fault in reverse
direction
STDIR
INTEGER
Direction of fault
UNREL
BOOLEAN
Residual voltage release of operation of directional
modes
Section 8
1MRK 502 048-UEN A
Current protection
204
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...