The interlocking module is connected to the surrounding functions within a bay as
shown in figure
Interlocking
modules in
other bays
Interlocking
module
SCILO
SCSWI
Apparatus control
modules
SXCBR
SCILO
SCSWI
SXSWI
Apparatus control
modules
SCILO
SCSWI
SXSWI
Apparatus control
modules
en04000526.vsd
IEC04000526 V1 EN
Figure 202:
Interlocking module on bay level
Bays communicate via the station bus and can convey information regarding the
following:
•
Unearthed busbars
•
Busbars connected together
•
Other bays connected to a busbar
•
Received data from other bays is valid
illustrates the data exchange principle.
Disc QB1 and QB2 closed
WA1 not earthed
WA2 not earthed
WA1 and WA2 interconn
Disc QB1 and QB2 closed
WA1 not earthed
WA2 not earthed
WA1 and WA2 interconn
. . .
. .
Station bus
QB1
WA1
WA2
Bay 1
Bay n
Bus coupler
WA1 unearthed
WA1 unearthed
WA1 and WA2 interconn
WA1 and WA2 interconn
in other bay
QB2
QA1
QB9
QB1
QB2
QA1
QB9
QB2
QB1
QA1
QC1
QC2
en05000494.vsd
IEC05000494 V1 EN
Figure 203:
Data exchange between interlocking modules
Section 12
1MRK 502 048-UEN A
Control
412
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...