Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim6
1 - 99999
A
1
1000
Rated CT primary current
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
Table 3:
TRM_8I_2U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim6
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint7
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec7
0.1 - 10.0
A
0.1
1
Rated CT secondary current
Table continues on next page
Section 3
1MRK 502 048-UEN A
Analog inputs
48
Technical manual
Содержание REG650 ANSI
Страница 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 42: ...36 ...
Страница 50: ...44 ...
Страница 64: ...58 ...
Страница 86: ...80 ...
Страница 262: ...256 ...
Страница 300: ...294 ...
Страница 438: ...432 ...
Страница 476: ...470 ...
Страница 592: ...586 ...
Страница 664: ...658 ...
Страница 678: ...672 ...
Страница 726: ...720 ...
Страница 727: ...721 ...