5 - Troubleshooting
Display Message Causes
Solution
W009
Table fail
NA
NA
W010
Fan Fail
(Alarm not shown
on the display;
there is only a flash
-
ing yellow LED)
This error appears when there is
malfunctioning of the fan(s) in-
side the inverter. In this condition,
the yellow LED on the front panel
flashes.
Error inside the inverter that cannot be resolved
with external operations. If the alarm is persistently
repeated, contact customer service.
W011
Bulk UV
Reading of the internal voltage
on the bulk capacitors carried out
when the inverter is connected to
the grid.
W012
Battery low
Low internal clock
battery voltage
Internal battery for maintenance
of the date/time settings is dis-
charged or damaged.
Replace the battery with the inverter completely
switched off (disconnect AC side and DC side) and
be sure to observe the correct polarity.
W013
Clk fail
Internal clock fail-
ure
The alarm appears when the
time shown on the display differs
by more than 1 minute from the
internal time of the microproces-
sors and indicates clock circuit
malfunctioning.
This is an error inside the inverter that cannot be
resolved with external operations. If the alarm is
persistently repeated, contact customer service.
W017
Jbox fail
Fuse-control board
fail (DC string fail)
Fuse(s) on the fuse boards is/are
damaged.
Using a multimeter, check the condition of the fus-
es (situated on the fuse boards).
Replace any open fuses and check that the input
current on the string(s) does not exceed the rat-
ing of the fuses (if string parallels have been made
outside the inverter).
If there are no damaged string fuses and the in-
verter continues to display the alarm message,
check whether the settings to be made through the
Aurora Manager software are correct (presence or
absence of one or more input strings).
W018
SPD DC protection
open
Overvoltage surge arresters situ-
ated on the DC side are dam-
aged.
Look at the inspection window present on each
surge arrester (DC side). If it is red, the surge ar-
rester is damaged and the cartridge must be re-
placed.
If the alarm status continues to be present even
though all the surge arresters have a green inspec-
tion window, contact customer service.
Содержание PVI-3.0-TL-OUTD-S-US
Страница 1: ...ABB solar inverters Product manual PVI 3 0 3 6 3 8 4 2 TL OUTD S US A 3 0 to 4 2 kW ...
Страница 16: ... 16 3005CC2 2 Installation location ...
Страница 32: ... 32 3007CC3 3 Mounting and wiring ...
Страница 62: ... 62 C011C5 5 Troubleshooting ...
Страница 66: ... 66 C012C6 6 Maintenance ...
Страница 72: ... 72 C013C7 7 Appendix Output power with one DC section operating ...