- 12 -
3003CC1
1- Introduction and safety
3.0 kW PVI-3.0-OUTD-US
PVI-3.0-OUTD-S-US
PVI-3.0-OUTD-S-US-A
•
Unit Weight -S version: 47.3 lbs/21.3kg
•
Dimensions (H x W x D) –S Version:
33.8” x 12.8” x 8.7”/
859mm x 325mm x 222mm
3.6 kW PVI-3.6-OUTD-US
PVI-3.6-OUTD-S-US
PVI-3.6-OUTD-S-US-A
3.8 kW
PVI-3.8-OUTD-S-US
PVI-3.8-OUTD-S-US-A
4.2 kW
PVI-4.2-OUTD-US
PVI-4.2-OUTD-S-US
PVI-4.2-OUTD-S-US-A
For inverters of equal output power, the difference between models is the presence of the wiring box and the
addition of Arc Fault Detection. A description of the three models can be found below.
Available versions
PVI-3.0-3.6-4.2-OUTD-US
No wiring box
PVI-3.0-3.6-3.8-4.2-OUTD-S-US
Wiring box with integrated DC disconnect switch
PVI-3.0-3.6-3.8-4.2-OUTD-S-US-A
Wiring box with integrated DC disconnect switch and
integrated PV AFCI Type 1 device for arc fault detection (AFD)
R
egulatory label
Technical data in this manual does
not supersede the data on the
labels affixed to the equipment.
The nameplate shown is affixed
to the inverter and provides the
following information:
1. Product origin
2. Model name
3. DC input data
4. AC output data
5. Certification
6. Environmental data
7. Protection
8. Adjustable parameters
UL 1741
CSA-C22.2 No. 107.1-01
C
US
®
Country of Origin Italy
www.abb.com/solar
SOLAR UTILITY INTERACTIVE
TRANSFORMERLESS INVERTER
MODEL: PVI-3.0-OUTD-S-US
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two
(2) this device must accept any interference received, including interference that may
cause undesidered operation.
Nominal Input Operating Voltage
Max. Input Voltage
Range of Input Operating Voltage
Range of Input Voltage @Full Power
Max. Input Current
Max. Input Short Circuit Current (P.V. Panels)
DC RATING
Nominal Output Voltage
Operating Voltage Range
Nominal Output Frequency
Operating Frequency Range
Output Power Factor
Max. Output Current
AC RATING
Max. Continuous Output Power
Max. Output Overcurrent Protection
2 x 10 A
2 x 12.5 A
360 V
600 V
90 - 580 V
200 - 530 V
60 Hz (factory preset)
59.3 ( ) - 60.5 ( ) Hz
1
2
>0.995
12 A / 14.5 A / 14.5 A (rms)
277 V~ / 240 V~ / 208 V~ 1Ø
15 A / 20 A / 20 A
3000 W @ 55°C amb.
244-304 V~/211-264 V~/183-228 V~
DC Ground Fault Detector/Interrupter is Provided
Operating Ambient Temperature: -25 to +60 °C (-13 to +140 °F), with Output Power Derating
Type of Enclosure: NEMA 4X
For more details about product specifications refer to the Instruction Manual
(
1
):
2
Adjustable from 57.0 Hz to 59.8 Hz
Adjustable from 60.2 Hz to 63.0 Hz
( ):
conditions: (1) this device may not cause harmful interference, and
1
2
3
4
5
7
8
6
Содержание PVI-3.0-TL-OUTD-S-US
Страница 1: ...ABB solar inverters Product manual PVI 3 0 3 6 3 8 4 2 TL OUTD S US A 3 0 to 4 2 kW ...
Страница 16: ... 16 3005CC2 2 Installation location ...
Страница 32: ... 32 3007CC3 3 Mounting and wiring ...
Страница 62: ... 62 C011C5 5 Troubleshooting ...
Страница 66: ... 66 C012C6 6 Maintenance ...
Страница 72: ... 72 C013C7 7 Appendix Output power with one DC section operating ...