- 41 -
C010CC4
4 - Operations
Parameter
Definition
Default
Value
Adjustable
Ranges
SET F conn< Indicates the value of the intermediate
under frequency set point to allow the
inverter to connect to the grid for the first
time.
59.3 Hz
59.8 Hz to
57 Hz
SET TIME
U>>
Indicates the value of the countdown
timer associated with the Absolute Over
Voltage setpoint U>>
0.16 sec
Fixed
SET TIME
U<<
Indicates the value of the countdown
timer associated with the Absolute Under
Voltage setpoint U<<
0.16 sec
Fixed
SET TIME
F>>
Indicates the value of the countdown
timer associated with the Absolute Over
Frequency setpoint F>>
0.16 sec
Fixed
SET TIME
F<<
Indicates the value of the countdown
timer associated with the Absolute Under
Frequency setpoint F<<
0.16 sec
Fixed
SET TIME U> Indicates the value of the countdown
timer associated with the Intermediate
Over Voltage setpoint U>
1 sec
0.16 sec to 5
sec
SET TIME U< Indicates the value of the countdown
timer associated with the Intermediate
Under Voltage setpoint U<
2 sec
0.16 sec to 5
sec
SET TIME F> Indicates the value of the countdown
timer associated with the Intermediate
Over Frequency setpoint F>
0.16 sec
0.16 sec to
300 sec
SET TIME F< Indicates the value of the countdown
timer associated with the Intermediate
Under Frequency setpoint F<
0.16 sec
0.16 sec to
300 sec
SET TIME
Conn 1
Indicates the time the inverter takes to
connect to the grid for the first time (not
after grid fault).
30 sec
1 sec to 3600
sec
SET TIME
Conn 2
Indicates the time the inverter takes to
connect to the grid after a grid fault.
300 sec
1 sec to 3600
sec
DISABLE U>> Provides ability to enable/disable the
Absolute Over Voltage Set point U>>
Enable
Disable or
Enable
DISABLE U<< Provides ability to enable/disable the
Absolute Under Voltage Set point U<<
Enable
Disable or
Enable
DISABLE F>> Provides ability to enable/disable the
Absolute Over Frequency Set point F>>
Enable
Disable or
Enable
DISABLE F<< Provides ability to enable/disable the
Absolute Under Frequency Set point F<<
Enable
Disable or
Enable
DISABLE U> Provides ability to enable/disable the In-
termediate Over Voltage Set point U>
Enable
Disable or
Enable
Содержание PVI-3.0-TL-OUTD-S-US
Страница 1: ...ABB solar inverters Product manual PVI 3 0 3 6 3 8 4 2 TL OUTD S US A 3 0 to 4 2 kW ...
Страница 16: ... 16 3005CC2 2 Installation location ...
Страница 32: ... 32 3007CC3 3 Mounting and wiring ...
Страница 62: ... 62 C011C5 5 Troubleshooting ...
Страница 66: ... 66 C012C6 6 Maintenance ...
Страница 72: ... 72 C013C7 7 Appendix Output power with one DC section operating ...