- 42 -
C010CC4
4 - Operations
Parameter
Definition
Default
Value
Adjustable
Ranges
DISABLE U>
(10 min)
Provides ability to enable/disable the
parameter
“SET U>(10 min)”
Disable
Disable or En-
able
Disable U<
Provides ability to enable/disable the In-
termediate Under Voltage Set point U<
Enable
Disable or En-
able
Disable F>
Provides ability to enable/disable the In-
termediate Over Frequency Set point F>
Enable
Disable or En-
able
Disable F<
Provides ability to enable/disable the In-
termediate Under Frequency Set point F<
Enable
Disable or En-
able
U>(10 min)
Der.
Provides ability to limit the power for 10
minutes due to the high average voltage
value set by the parameter “SET U>(10
min)”
Disable
Disable or En-
able
Slow Ramp
Provides ability to slowly ramp the Output
Power at connection( Soft start)
Disable
Disable or En-
able
OF Derating
Provides ability to limit the Output Power
due to the high grid frequency
Disable
Disable or En-
able
Reset Country
S
Provides ability to reset the country code Not Appli-
cable
Not Applicable
New PW
- Used to change the password for accessing the SETTINGS menu. The default
password is 0000 and can be changed using the display keyboard.
•
Use ENTER to scroll the digits (from left to right)
•
Use ESC to return to the previous digit (from right to left)
•
Press ESC several times to return to the previous menus
•
Use DOWN to progressively scroll the numerical scale downwards (from 9 to 0)
Be careful to memorize the new password. For security purposes there is no reset function.
If the password is misplaced it will not be possible to access the inverter.
Cash
- Used to set the name of the currency and the value given to 1 kWh of energy
produced. The correct setting of these parameters displays the actual earning/saving given
by the system.
•
Name: the chosen value is set (default is $, USD).
•
Val/KWh: indicates the cost/incentive of 1 KWh expressed in the chosen currency (default
is 0.16).
Time
– Used to set the current date and time (daylight saving time not included).
Language
– Used to set the menu language.
Vstart
– Used to set the Vstart voltage (separately for both channels if they are configured in
independent mode). Change the activation voltage only if necessary. A configuration program
that can help to correctly size the photovoltaic system is available on the website.
Содержание PVI-3.0-TL-OUTD-S-US
Страница 1: ...ABB solar inverters Product manual PVI 3 0 3 6 3 8 4 2 TL OUTD S US A 3 0 to 4 2 kW ...
Страница 16: ... 16 3005CC2 2 Installation location ...
Страница 32: ... 32 3007CC3 3 Mounting and wiring ...
Страница 62: ... 62 C011C5 5 Troubleshooting ...
Страница 66: ... 66 C012C6 6 Maintenance ...
Страница 72: ... 72 C013C7 7 Appendix Output power with one DC section operating ...