- 52 -
C01
1C5
5 - Troubleshooting
Display Message Causes
Solution
E005
Comm.Error
Internal Communi-
cation Error
The alarm occurs when there
are communication problems be-
tween the control devices inside
the inverter.
Error inside the inverter that cannot be checked ex-
ternally. If the problem persists (after switching the
inverter off and then on again), contact customer
service.
E006
Output OC
Output Overcurrent
The alarm appears when the in-
verter output current exceeds the
output overcurrent threshold of
the inverter.
Error inside the inverter that cannot be checked ex-
ternally. If the problem persists (after switching the
inverter off and then on again), contact customer
service.
E007
IGBT Sat
IGBT Saturation
The alarm appears when one of
the active devices of the inverter
is in saturation state.
Once the error appears, the inverter attempts to
resume normal operation. If the error occurs spo-
radically, it may be caused by a sharp transition of
the grid voltage or the input voltage but is not at-
tributable to inverter malfunctioning. If the error is
associated with an internal fault, it will continue to
appear; contact customer service.
E009
Internal error
Error inside the inverter
Error inside the inverter that cannot be checked ex-
ternally. If the problem persists (after switching the
inverter off and then on again), contact customer
service.
E010
Bulk Low
Low Bulk Voltage
Voltage at a specific part of in
-
verter input circuit is not sufficient
for grid connection.
The alarm can be triggered by
causes external to the inverter:
a low inverter input voltage (just
above the activation voltage) that
is not accompanied by sufficient
availability of power from the pho-
tovoltaic array (typical condition
of periods of insufficient sunlight).
If the error warning appears sporadically, it can be
attributed to causes external to the inverter (insuf-
ficient sunlight, and therefore little power available
from the PV array).
If the problem appears systematically even in con-
ditions of high sunlight and with input voltage sig-
nificantly higher than the activation voltage, contact
customer service.
E011
Ramp Fail
Bulk ramp timeout
Error inside the inverter regarding
the time for starting steady state
operation of the DC-DC circuit
part (Boost).
It can be caused by an external
string voltage too low or due to
reduced power from PV arrays
(typically in the morning).
If the alarm is present early in the morning it could
be useful to increase the starting voltage to al-
low the grid connection of the inverter when more
power is available from the PV array. If the problem
persists (after switching the inverter off and then on
again), contact customer service.
E012
DcDc Fail
Boost module error
Error inside the inverter regard-
ing the operation of the DC-DC
circuit part (Boost).
Error inside the inverter that cannot be checked ex-
ternally. If the problem persists (after switching the
inverter off and then on again), contact customer
service.
Содержание PVI-3.0-TL-OUTD-S-US
Страница 1: ...ABB solar inverters Product manual PVI 3 0 3 6 3 8 4 2 TL OUTD S US A 3 0 to 4 2 kW ...
Страница 16: ... 16 3005CC2 2 Installation location ...
Страница 32: ... 32 3007CC3 3 Mounting and wiring ...
Страница 62: ... 62 C011C5 5 Troubleshooting ...
Страница 66: ... 66 C012C6 6 Maintenance ...
Страница 72: ... 72 C013C7 7 Appendix Output power with one DC section operating ...