4 - Operations
Parameter
Definition
Default
Value
Adjustable
Ranges
SET U>>
Indicates the value of the absolute over
voltage set point beyond which the in-
verter disconnects from the grid. [120%
of Nominal line to neutral Voltage]
120% of
Nominal line
to neutral
Voltage
Fixed
SET U<<
Indicates the value of the absolute under
voltage set point below which the inverter
disconnects from the grid [50% of Nomi-
nal line to neutral Voltage]
50% of
Nominal line
to neutral
Voltage]
Fixed
SET F>>
Indicates the value of the absolute over
frequency set point beyond which the
inverter disconnects from the grid
60.5 Hz
Fixed
SET F<<
Indicates the value of the absolute un-
der frequency set point below which the
inverter disconnects from the grid
57 Hz
Fixed
SET U>
Indicates the value of the intermediate
over voltage set point beyond which the
inverter disconnects from the grid [110%
of Nominal line to neutral Voltage]
110% of
Nominal line
to neutral
Voltage
Fixed
SET U>(10
min)
Inverter disconnects from the grid after 10
minutes in case the average grid voltage
overcomes the threshold value(305V)
110% of
Nominal line
to neutral
Voltage]
(110% x V
LN
)
to
(115% x V
LN
)
SET U<
Indicates the value of the intermediate
under voltage set point below which the
inverter disconnects from the grid [88% of
Nominal line to neutral Voltage]
88% of
Nominal line
to neutral
Voltage]
Fixed
SET F>
Indicates the value of the intermediate
over frequency set point beyond which
the inverter disconnects from the grid
60.5 Hz
60.2 Hz to
63.0 Hz
SET F<
Indicates the value of the intermediate un-
der frequency set point below which the
inverter disconnects from the grid
59.3 Hz
59.8 Hz to
57 Hz
SET U Conn> Indicates the value of the intermediate
over voltage (line to neutral) set point to
allow the inverter to connect to the grid for
the first time.
110% of
Nominal line
to neutral
Voltage]
(110% x V
LN
)
to
(115% x V
LN
)
SET U conn< Indicates the value of the intermediate
under voltage (line to neutral) set point to
allow the inverter to connect to the grid for
the first time.
88% of
Nominal line
to neutral
Voltage
(50% x V
LN
)
to
(88% x V
LN
)
SET F conn> Indicates the value of the intermediate
over frequency set point to allow the
inverter to connect to the grid for the first
time.
60.5 Hz
60.2 Hz to
63.0 Hz
Содержание PVI-3.0-TL-OUTD-S-US
Страница 1: ...ABB solar inverters Product manual PVI 3 0 3 6 3 8 4 2 TL OUTD S US A 3 0 to 4 2 kW ...
Страница 16: ... 16 3005CC2 2 Installation location ...
Страница 32: ... 32 3007CC3 3 Mounting and wiring ...
Страница 62: ... 62 C011C5 5 Troubleshooting ...
Страница 66: ... 66 C012C6 6 Maintenance ...
Страница 72: ... 72 C013C7 7 Appendix Output power with one DC section operating ...