550-UH User’s Manual
1-97
Parameters
1106
REF2 SELECT
0…17, 19…21
1
19 (
PID
1
OUT
)
Selects the signal source for external reference
REF
2.
0…17 – Same as for parameter 1103
REF
1
SELECT
.
19 =
PID
1
OUT
– The reference is taken from the
PID
1 output. See
and
.
20…21 – Same as for parameter 1103
REF
1
SELECT
.
1107
REF2 MIN
0.0…100.0%
0.1%
0.0%
(0.0…600.0% for toruqe)
Sets the minimum for external reference 2.
• The minimum analog input signal (in volts or amperes) corresponds to
REF
2
MIN
in %.
• Parameter 1301
MINIMUM
AI
1 or 1304
MINIMUM
AI
2 sets the minimum analog input signal.
• This parameter sets the minimum frequency reference.
• The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque.
1108
REF2 MAX
0.0…100.0%
0.1%
100.0%
(0.0…600.0% for torqe)
Sets the maximum for external reference 2.
• The maximum analog input signal (in volts or amperes) corresponds to
REF
2
MAX
in %.
• Parameter 1302
MAXIMUM
AI
1 or 1305
MAXIMUM
AI
2 sets the maximum analog input signal.
• This parameter sets the maximum frequency reference.
• The value is a percentage of the:
– maximum frequency or speed
– maximum process reference
– nominal torque.
Group 11: Reference Select
Code Description Range
Resolution
Default
S
19=
PID
1
REF
2
SELECT
LIMIT
MAX
(1107, 1108)
MIN
(1107, 1108)
PFA
If PFA is used
1…17
20…21
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...